Descriptions:
NV-EVAC-FAE-RM628 is a core management and control device for public address
broadcasting and emergency voice alarm broadcasting. It can be directly controlled and
system status checked on a 5-inch HD touch screen. It support user-defined function and
system control through PC management software, automatic monitoring and management
to physical partition status and terminal equipment, automatic executing the.
pre-programming control, etc.Built-in programmable trigger input and output interfaces,
to achieve integrated control to the sound-light alarm module (as well as connected to the
bus fire linkage controller).
Features:
▪ 5 inch HD color touch graphical man-machine operation interface.
▪ One button for emergency alarm.
▪ Support zone selection, zone distribution, grouping operation, with independent zone
volume adjustment.
▪ Support user-defined zone name, group name, host name (multi-host network), easy
to operate and manage.
▪ Support event trigger, timing trigger control output.
▪ Support zone monitor, equipment status real-time indication.
▪ Support event trigger phone call notification, can be set re-calling times when no
answering.
▪ Integrated 4 independent players (supports MP3 and WMA audio formats).
▪ Support lines redundant wiring.
▪ Support Ethernet online configuration, control interface work offline.
▪ Support up to 4 remote microphones at max distance 600 meters , and support a
microphone circuit redundancy wiring.Support linkage to bus fire controller (fanhai
Sanjiang 9100 and 9000 series of fire linkage controller).
Basic Functions:
▪ Integrated 1 independent background music player, support timing, fixed, curved,
specify playback modes, support MP3 and WMA audio formats.
▪ Integrated 1 independent voice message player, support voice message and language
revision as demand.
▪ Integrated 2 independent EVAC voice message players; support programmable stage
evacuation alarm mode and specified partition evacuation alarm mode, evacuation
alarm and warning information can be played at the same time.
▪ Integrated 1 channel analog telephone interface for remote telephone paging
▪ broadcast.
▪ With 4 line inputs (one is optional for line or ordinary microphone), 1 audio
▪ output,which can be connected to external recorder, for emergency paging recording.
▪ With 4 remote MIC interfaces, connected to NV-EVAC-FAE-RM628 and
NV-EVAC-FAE-RM628 remote microphone by standard RJ-45 and CAT-5 cable, adapting
long distance parallel transmission mode for language transmission, up to 600 meters.
▪ With 8 level signal or 0 voltage short circuit input (or voltage from the programming
decision, default 0 voltage), (can be regarded as 8 shortcut control keys), each
▪ shortcut key functions can be user-defined , such as: play language message to speci-
fied zones or open external power supply to trigger a third party equipment to
achieve the event triggering alarm.
▪ Real time diagnosis, handling, record≤ 1000, support sound, light alarm and prompt
maintenance, troubleshooting when abnormal.
▪ Support basic Window platform visual operation interface, status automatic
▪ synchronization, classification rights management to ensure the security system.
▪ System support the third party online 0 voltage relay input and output interface.
▪ Host has a full backup function, by adding another host, also can be based on the
“cloud” architecture, not only to ensure the system to be more safe , but also to
expand system control points (Note: Configure NV-EVAC-FAE-RM628 before adding
devices, otherwise the added host cannot operate and work normally, the host will
automatically prompt the user to configure).
Specification:
Electrical Specifications | |
AC Power Supply | |
Voltage | ~220-240V 50/60Hz |
Maximum Current | Less than 0.2A |
Fuse Specification | 250V/2A, slow type |
Power | 6W |
DC Power Supply | |
Voltage | 24V DC, ±20% |
Maximum Current | 1.5 A |
Performance Index | |
Emergency Microphone | 1.5 A |
Sensitivity5mV | 5mV |
Impedance | 600Ω |
Line input | |
Distortion | <1%(rated output power),1KHz |
Frequency | 80Hz~20KHz |
Sensitivity | 350mV |
Impedance | 10KΩ |
S/N Ratio | >70dB |
Record Output | |
Distortion | <1% (rated output power),1KHz |
Frequency | 200mV |
Sensitivity | >70dB |
Contact Output | |
Fault Relay Output | Short circuit, no voltage |
Fire linkage Relay Output | Short circuit, no voltage |
8 Relay Programmable Output | Short circuit, no voltage |
Programmable DC24V Power Outputs | +DC 24V, 1A |
8 Programmable Trigger Input | |
Level Model | highest 3.3V |
Short Circuit Mode | Short circuit, no voltage |
Short Circuit Input | |
Fire Reset Input Contact | Pulse≥0.5S, no voltage |
Voice Message | |
Data Format | MP3 or WMA format |
Storage Type | SD |
Information Capacity | 65535 |
Storage Time | >10 years |
Log Information | |
Data Format | HEX |
Storage Type | Nand Flash |
Information Capacity | 2000 |
Storage Time | >10 years |
Mechanical Index | |
Size (L x W x D) | 484 x 132 x 449 mm (19 inches wide, 3U) |
Weight | About 8.0 Kg |
Installation | Desktop or 19 inch cabinet |
Color | Black |
Environmental Requirements | |
Operating Temperature | +5oC ~ +40oC |
Storage Temperature | -20oC ~ +70oC |
Relative Temperature | <95% |