Features:
• Built-in 500W amplifier, with 8 zones and A+B independent dual speaker loop output,
each zone has independent LED indicator light, output control button and volume
adjustment.
• Audio processing with 6 general audio inputs and 1 MP3 input, it can connect with
external microphone, CD player, tuner and etc, it can play any audio source in any zone.
Among them, 2 channels have 24V phantom power microphone input, 4 channels are
AUX input and 1 channel is MP3 audio channel from the controller.
• With fault self-check of power-on system, and fault full check of manual system
• function.
• With real-time indication of system status.
• Connecting with one backup amplifier, when built-in amplifier damaged, it will switch
to backup amplifier automatically.
• Automatically monitor every zone speaker loop status (open circuit, short circuit) in
real-time.
• 8-channel short-circuit/level trigger mode, the trigger response can be configured with
3 different channels of EVAC, ALERT, and LINE3, and the output can be arbitrarily
• configured with partition, group, and short-circuit contact combination.
• Support external 24V backup power supply, realize power-off continuous normal
• operation without delay.
• Extension port can connect controller and next extension device.
• The partition output has three-wire and four-wire forced-cut adjustment functions.
Specification:
Rated Power Output | 500W |
Output Voltage | 100V |
MIC1-2 Input Distortion | <1% (output rating), 1KHz |
MIC1-2 Input Frequency Response | 80Hz~20KHz |
MIC1-2 Input Sensitivity | 5mV/6/600Ω |
MIC1-2 Input SNR | >65dB |
AUX3-6 Input Distortion | <1% (output rating), 1KHz |
AUX3-6 Input Frequency Response | 80Hz~20KHz |
AUX3-6 Input Sensitivity | 350mV/10kΩ |
AUX3-6 Input SNR | >70dB |
Spare Amplifier Input | 100V |
Spare Amplifier Audio Signal Output | ±385mV (balanced output) |
Alarm Input | 8 |
Alarm Output | 8 |
Zone Input | 8 |
24V Relay Output | 8 |
Short Circuit mode | short circuit |
Type of cooling | air-cooled |
Guard mode | delay/overheat/ short circuit/ overload |
Output Volume Control | 6 |
Supply Voltage | ~ 220V-240V, 50/60Hz |
Maximum Current | 3A |
Fuse Size | 250V/5A, slow type |
Spare Voltage | 24V DC, ±20% |
Maximum Current | 30A |
Maximum Power Consumption | 600W |
Dimensions (L x W x D) | 484x88x353mm |
Weight | 10.5kg |
Installation method | Desktop or 19″ cabinet |
Connectors:
1. Power switch.
2. AC power outlet.
3. DC 24V input interface.
4. Fire alarm trigger output node.
5. Fire alarm trigger input node.
6. 3 wire power amplifier 100V output.
7. 485 Online interface.
8. DC 24V output.
9. Unplug code switch from computer address.
10. Backup power amplifier 100V input.
11. Backup power amplifier signal output.
12. SYS C
13. Impedance correction button.
14. 6 way background music input.
▪ System fault output, When something goes wrong, This port will be closed.
▪ Fire alarm output, When the fire alarm is triggered, This port will be closed.
▪ Emergency reset input, Short circuit interface, Fire alarm will be reset